Abstract
The purpose of this study was to evaluate the resolution and accuracy of PCBs in the transformer oil using simple cartridge pretreatment method. Also, purification ability of PCB free oils was investigated. The average recovery rate of 142 PCB congeners was 82.2%. And, average recovery rate and relative standard deviation (%RSD) of tri- to hepta- chlorinated biphenyl congener were 94.3% and below 18.5%, respectively. Average recovery of IUPAC No. 189, the surrogate for this method were 99.9%. Also, the recovery rate of 10 dioxinlike PCB congeners was 93.4%. In addition, this simple cartridge pretreatment method showed high purifying ability of interferences in PCB free oils. The recovery rate and %RSD of 39 PCB congeners in 7 PCB free oil were 85.3% and 5.3%. Further, recovery rate and %RSD of tri- to hepta- chlorinated biphenyl congener were 97.2% and 4.8%, respectively. Simple cartridge pretreatment method in this study showed high accuracy.
Key Words: Transformer oil, PCBs, Homologue, Rapid analysis method, Dioxin like-PCBs, Recovery rate
TOOLS
Share :
Facebook Twitter Linked In Google+ Line it
METRICS Graph View
  • 517 View
  • 2 Download
Related articles in
J Environ Anal Health Toxicol


ABOUT
ARTICLE CATEGORY

Browse all articles >

BROWSE ARTICLES
EDITORIAL POLICY
FOR CONTRIBUTORS
Editorial Office
Hansin B/D 305 MapoDeae-ro 12, Mapo-Goo, Seoul, 04175 Korea
Tel: +82-2-704-4801    Fax: +82-2-704-4802    E-mail: ksfea7044801@gmail.com                

Copyright © 2024 by Korea Society of Environmental Analysis. All rights reserved.

Developed in M2PI

Close layer
prev next